LINKQNET TRUE ONLINE PURE SINEWAVE TOWER SERIES UPS (1KVA ~ 3KVA)

FEATURES:

  • Online double conversion
  • High power density
  • Online double conversion with full digital control
  • Wide input voltage range:110~300Vac
  • Input power factor 0.99 with PFC
  • Selectable output voltage: 208/220/230/240Vac
  • Smart charger design for optimized battery performance
  • Maximum charging current can be expanded to 12A (Long run unit)
  • Emergency power off function (EPO)
  • ECO mode operation for energy saving
  • Generator compatible
  • Cold start
  • Intelligent fan speed regulation
  • Versatile LCD human-computer interface
  • Multiple communication interface:RS232 (USB/EPO/Relay card/SNMP card optional)
  • Multiple protection function:short-circuit,overload,overheat, battery overcharge and overdischarge, output low voltage and fan fault alarm

LinkQnet True Online Pure Sinewave Tower Series UPS (1kVA ~ 3kVA)

The LinkQnet 1 ~ 3kVA Online UPS Series are Reliable (Online Double Conversion, PF:0.99) and Compact in Size.
Thanks to the New Battery Discharge Protection Control Function, It is Perfect for Medium Voltage Substation Applications.

FEATURES:

  • Online double conversion
  • High power density
  • Online double conversion with full digital control
  • Wide input voltage range:110~300Vac
  • Input power factor 0.99 with PFC
  • Selectable output voltage: 208/220/230/240Vac
  • Smart charger design for optimized battery performance
  • Maximum charging current can be expanded to 12A (Long run unit)
  • Emergency power off function (EPO)
  • ECO mode operation for energy saving
  • Generator compatible
  • Cold start
  • Intelligent fan speed regulation
  • Versatile LCD human-computer interface
  • Multiple communication interface:RS232 (USB/EPO/Relay card/SNMP card optional)
  • Multiple protection function:short-circuit,overload,overheat, battery overcharge and overdischarge, output low voltage and fan fault alarm

SPECIFICATIONS:

Capacity: 1000VA/900W 3000VA/2700W
INPUT:
Nominal Voltage: 208/220/230/240Vac
Input Voltage Range: 110~300Vac (176~280Vac @ 100% load)
Frequency Range: 40~70Hz (50/60Hz Auto-Sensing)
Power Factor: ≥0.99
OUTPUT:
Output Voltage: 208/220/230/240Vac
Power Factor: 0.9
Voltage Regulation: ±1%
Output Frequency:
Line Mode: 46~54Hz or 56~64Hz
Bat. Mode: (50/60±0.1%)Hz
Crest Factor: 03:01
Harmonic Distortion (THDv): ≤3% Linear load
≤5% Non linear load
Transfer Time:
AC mode to Bat Mode: 0ms
Inverter to Bypass: 4ms (Typical)
Output Waveform: Pure Sinewave
EFFICIENCY:
AC Mode: 88% 91%
Battery Mode: 85% 88%
BATTERY:
Battery Number: 2 6
Capacity (Standard Unit): Standard Run models have internal 9Ah/12V VRLA Batteries Installed. Extended Run models cannot accept internal batteries and require an external battery solution.
Typical Recharging Time: 4 hours (to 90% of full capacity)
Charging Voltage: 27.4Vdc±1% 82.2Vdc±1%
Charging Current (Max.): 1A
INDICATORS:
LED Display: Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
LCD Display: Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time
Alarm:
Battery Mode: Beeping every 4 seconds
Battery Low: Beeping every second
Overload: Beeping twice every second
Fault: Continuously beeping
Physical:
Dimensions W × D × H (mm): 144 × 293 × 209 191 × 460 × 337
Net Weight (kg): 9.3 24.5
Environment:
Operating Temperature: 0°C~40°C
Storage Temperature: -25°C~55°C
Humidity Range: 20~95%RH @ 0~40°C (Non condensing)
Altitude: 1500m
Noise Level: <50db at 1 Meter
Standards:
Safety: IEC/EN62040-1,IEC/EN62477-1
EMC: IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8
0
Linkqage