LINKQNET 3KVA 72V MP XRT 2U RACKMOUNT ONLINE UPS – REQUIRES BATTERIES

FEATURES:

  • Rack/Tower convertible design online double conversion with full digital control
  • Wide input voltage range: 110~300Vac
  • Input power factor 0.99 with PFC
  • Selectable output voltage: 208/220/230/240Vac
  • Smart charger design for optimized battery performance
  • Maximum charging current can be expanded to 12A (Long run unit)
  • Emergency power-on function (EPO)
  • ECO mode operation for energy saving
  • Generator compatible
  • Hot-Swappable battery design
  • Cold start
  • Intelligent fan speed regulation
  • Load segment settable (Optional)
  • Versatile LCD human-computer interface
  • Multiple communication interfaces: RS232 (USB/EPO/Relay card/SNMP card optional)
  • Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm

1 in stock

LinkQnet 3KVA 72V MP XRT 2U Rackmount Online UPS - Requires Batteries

FEATURES:

  • Rack/Tower convertible design online double conversion with full digital control
  • Wide input voltage range: 110~300Vac
  • Input power factor 0.99 with PFC
  • Selectable output voltage: 208/220/230/240Vac
  • Smart charger design for optimized battery performance
  • Maximum charging current can be expanded to 12A (Long run unit)
  • Emergency power-on function (EPO)
  • ECO mode operation for energy saving
  • Generator compatible
  • Hot-Swappable battery design
  • Cold start
  • Intelligent fan speed regulation
  • Load segment settable (Optional)
  • Versatile LCD human-computer interface
  • Multiple communication interfaces: RS232 (USB/EPO/Relay card/SNMP card optional)
  • Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm

SPECIFICATIONS:

Capacity 3000VA/ 2700W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~280Vac @ 100% load)
Frequency range 40~70Hz  (50/60Hz Auto-Sensing)
Power factor ≥0.99
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
Output frequency Line Mode 46~54Hz or 56~64Hz
Bat. Mode (50/60±0.1%)Hz
Crest factor 3:01
Harmonic distortion (THDv) ≤3% Linear load
≤5% Non linear load
Transfer time AC mode to Bat.Mode 0ms
Inverter to Bypass 4ms (Typical)
Output waveform Pure Sinewave
EFFICIENCY
AC mode 92%
Battery mode 88%
BATTERY
12V Series Battery number 6 (72V)
Battery Capacity (typical) 9Ah to 200Ah
Typical recharging time 4 hours (to 90% of full capacity based on battery capacity)
Charging voltage 82.2Vdc±1%
Charging current (Max) 12A
INDICATORS
LED display Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload and UPS fault
LCD display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage,
Battery voltage, Inner temperature and Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping