LINKQNET 2KVA 48V MP RT 2U RACKMOUNT ONLINE UPS WITH 4× 9AH BATTERIES

FEATURES:

 

  • Rack/Tower convertible design online double conversion with full digital control
  • Wide input voltage range: 110~300Vac
  • Input power factor 0.99 with PFC
  • Selectable output voltage: 208/220/230/240Vac
  • Smart charger design for optimized battery performance
  • Maximum charging current can be expanded to 12A (Long run unit)
  • Emergency power-on function (EPO)
  • ECO mode operation for energy saving
  • Generator compatible
  • Hot-Swappable battery design
  • Cold start
  • Intelligent fan speed regulation
  • Load segment settable (Optional)
  • Versatile LCD human-computer interface
  • Multiple communication interfaces: RS232 (USB/EPO/Relay card/SNMP card optional)
  • Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm

Out of stock

LinkQnet 2KVA 48V MP RT 2U Rackmount Online UPS with 4× 9Ah Batteries

FEATURES:

  • Rack/Tower convertible design online double conversion with full digital control
  • Wide input voltage range: 110~300Vac
  • Input power factor 0.99 with PFC
  • Selectable output voltage: 208/220/230/240Vac
  • Smart charger design for optimized battery performance
  • Maximum charging current can be expanded to 12A (Long run unit)
  • Emergency power-on function (EPO)
  • ECO mode operation for energy saving
  • Generator compatible
  • Hot-Swappable battery design
  • Cold start
  • Intelligent fan speed regulation
  • Load segment settable (Optional)
  • Versatile LCD human-computer interface
  • Multiple communication interfaces: RS232 (USB/EPO/Relay card/SNMP card optional)
  • Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm

SPECIFICATIONS:

 

Capacity 2000VA/1800W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~264Vac @ 100% load)
Power factor ≥0.99
FREQUENCY
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
OUTPUT
Output voltage 208/220/230/240Vac
Voltage regulation ±1%
Power factor 0.9
Output frequency Line mode 46~54Hz or 56~64Hz
Battery mode (50/60±0.1%)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤3% Linear load
≤5% Non linear load
Transfer time AC mode to Battery mode 0ms
Inverter to Bypass 4ms (Typical)
Output waveform Pure Sinewave
EFFICIENCY
AC mode 0.91
Battery mode 0.87
BATTERY
Battery number 4
Capacity (Standard unit) 9Ah 12V
Typical recharging time 4 hours (To 90% of full capacity)
Charging voltage 54.8Vdc±1%
Charging current (Max.) 1A
INDICATORS
LED display Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
LCD display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W × D × H 440 × 460 × 86.5mm
Net weight 19.5kg
ENVIRONMENT
Operating temperature 0°C~40°C
Storage temperature -25°C~55°C
Humidity range 20~95%RH @ 0°C~40°C (Non condensing)
Altitude <1500m, derating required when>1500m
Noise level <50dB at 1 Meter
STANDARDS
Safety IEC/EN 62040-1, IEC/EN 62477-1
EMC IEC/EN 62040-2 (IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2)
1. When output voltage is 208Vac, need to derate to 80% of the unit capacity
2. Specifications are subject to change without prior notice
3. Data above are typical values for reference only, not as a basis for engineering design