2KVA 1600W ONLINE TOWER UPS WITH 4X12V9AH BATTERIES

FEATURES: 

  • True double-conversion
  • Microprocessor control optimizes reliability
  • Input power factor correction
  • Output power factor 0.8
  • Wide input voltage (110 V – 300 V)
  • Converter mode available
  • ECO mode for energy saving (Only available for 1-3KVA)
  • Generator compatible
  • Adjustable battery number only available for 6K and up models
  • Smart SNMP works well with either USB or RS-232 together
  • Emergency power off function (EPO) only available for 6K/10K models
  • Optional isolation transformer available

Out of stock

SKU: UPS-ONLINE-2000VA-LQ Categories: , , , Tags: , , ,

2kVa 1600W Online Tower UPS with 4X12V9Ah Batteries

Features: 

  • True double-conversion
  • Microprocessor control optimizes reliability
  • Input power factor correction
  • Output power factor 0.8
  • Wide input voltage (110 V – 300 V)
  • Converter mode available
  • ECO mode for energy saving (Only available for 1-3KVA)
  • Generator compatible
  • Adjustable battery number only available for 6K and up models
  • Smart SNMP works well with either USB or RS-232 together
  • Emergency power off function (EPO) only available for 6K/10K models
  • Optional isolation transformer available.
SPECIFICTATIONS
Phase Single phase with ground
Capacity 2000 VA / 1600 W
INPUT
Nominal Voltage:
Input Voltage Range:

Frequency Range:

Power Factor:
100/110/115/120/127VAC or 200/208/220/230/240VAC
55-150 VAC or 110-300 VAC (Based on load at 50%)
85-140VAC or 160-280VAC (Based on load at 100%)
40 Hz ~ 70 Hz
≧0.99 @ Nominall Voltage (100% load)
OUTPUT
Output Voltage:

Voltage Regulation:
Frequency Range (Synchronized Range):
Frequency Range (Batt. Mode):
Current Crest Ratio:
Harmonic Distortion:

AC Mode to Battery Mode Transfer Time:
Inverter to Bypass Transfer Time:
Waveform (Batt. Mode):
100/110/115/120/127VAC or 200/208/220/230/240VAC
± 1 %
47~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
3:1
≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load)
Zero
4 ms (Typical)
Pure Sinewave
EFFICIENCY
AC Mode:

Battery Mode:
88%
87%
BATTERY
Battery Type:
Numbers:
Typical Recharge Time:
Charging Current (max.):
Charging Voltage:
12 V / 9 Ah
4
4 hours recover to 90% capacity
1 A
54.7 VDC ±1%
INDICATORS
LCD:
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery Mode:
Low Battery:
Overload:
Fault:
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
Dimensions 397 x 145 x 220 mm
17 kg
ENVIRONMENT
Humidity:
Noise Level:
20-90 % RH @ 0- 40°C (Non-condensing)
Less than 50dB @ 1 Meter
MANAGEMENT
Smart RS-232 / USB:
Optional SNMP:
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC
Power management from SNMP manager and web browser
0